Skip to content
Contact

DALI · Interface guide

Factory

Service controls for Aeron staff. The station's internal service logs, and the RS232 service console.

The Factory page holds service controls that Aeron staff use to look into a station that misbehaves. The page itself says it: changes here affect the station's behaviour directly.

Who can open it: Factory only. Anyone else who reaches it sees "Access denied".

Daemon Logs

The station runs a set of background services (daemons): one for each kind of data source, for logging, for uploads and so on. This card lists them, one per row.

ColumnWhat it shows or does
DaemonThe service.
ProcessWhether the service is running and doing its work.
LoggingWhether the service writes log files. Takes effect within about 30 seconds of saving, with no restart.
Last LogWhile logging is on, when the service last wrote to its log. A time that keeps growing means it is idle or stopped.
LevelDEBUG, INFO, WARN or ERROR: how much detail goes in the log.
Debug FlagsExtra detail switches, where a service has them.
ActionRestart restarts that service. Clear deletes its log files.
ButtonWhat it does
Save AllSaves the logging settings of every row.
Restart AllRestarts every service, after you confirm. Expect a gap in the data of about 5 seconds.
Clear All LogsDeletes every service's log files from internal memory and the SD card, after you confirm. Cannot be undone.

Detailed logging uses storage. Turn it back down when the investigation is over.

Serial Console (RS232)

The station's RS232 port can be either a Modbus port or a service console.

StateWhat the port does
ONThe port is a service console, for start-up messages and recovery.
OFFThe port is free for the RS232 Modbus master or slave (normal use).

Turn ON and Turn OFF switch it, after you confirm. Turning on RS232 Master or RS232 Slave on the Modbus page switches the console off by itself.