DALI · Interface guide

Sensors

The Sensor Inventory. A record of every sensor fitted to the station, which input it is connected to, and when its calibration is due.

The Sensor Inventory (Sensor Inventory in the sidebar) is the station's record of its physical sensors: serial number, make and model, which input each one is wired to, when it was installed and calibrated, and when the next calibration is due. It is a register for audits and maintenance. It does not change how readings are taken, with one exception described below for pyranometers.

Who can open it: Admin and Factory.

Sensor table

ColumnWhat it shows
SerialThe sensor's serial number.
Make, ModelManufacturer and model.
SourceThe input the sensor is connected to, for example "Modbus RS485 / Slave 3", "SDI-12 / Addr 0", "Analog Ch 2" or "Digital Ch 1".
SensitivityShown only when a sensor has one: the pyranometer sensitivity in microvolts per W/m².
Cal date, Cal due, InstallCalibration date, calibration due date and install date.
Cal StatusOK, Due soon (due within 30 days) or Overdue (the due date has passed), judged against the station's date.

Each row has Edit and Delete. Delete asks you to confirm.

ButtonWhat it does
Add SensorOpens an empty form under the table.
Download ReportMakes a PDF of the inventory in your browser.

Add or edit a sensor

Fields marked with a red star are required.

FieldAllowed valuesWhat it does
TypeModbus, SDI-12, Analog, DigitalThe kind of input. Changing it reloads the Source list.
Source *One of the station's inputs of that type that is not already linked to another sensorWhich input the sensor is wired to.
Sensitivity *A number greater than 0. Shown only for a differential (millivolt) analog channel.The pyranometer's sensitivity from its calibration certificate, in microvolts per W/m².
Serial No. *Up to 64 charactersThe sensor's serial number.
Make *Pick from the list, or Add new... (up to 48 characters)Manufacturer. A new make is added to the list for next time.
Model *Pick from the list, or Add new... (up to 48 characters)Model. The list follows the make you picked.
Calibration date *A date within 100 years of todayWhen the sensor was last calibrated.
Calibration due dateA date within 100 years of today, not before the calibration dateWhen the next calibration is due. Setting the install date fills this in as install date plus 2 years; you can change it.
Install date *A date within 100 years of todayWhen the sensor was fitted.

Save stores the sensor. Cancel closes the form.

Sensitivity changes the channel

Saving a sensitivity also sets that analog channel's Scaling to match (1,000,000 divided by the sensitivity), so readings follow the new certificate straight away. Check the channel on Analog and digital after you save.

Messages you may see

MessageWhat it means
Select a source.Pick the input the sensor is on.
That source is already mapped to another sensorEach input can belong to one sensor. Edit or delete the other sensor first.
Sensitivity is required for differential (mVolt) channels and must be greater than 0.Enter the certificate value.
Serial number is required. / Make is required. / Model is required.Fill in the field.
Calibration date is required. / Install date is required.Fill in the date.
Calibration due date cannot be before calibration date.Correct one of the dates.
No sensors to export.The inventory is empty, so there is no report to make.