How data flows

What happens to a reading from the moment a sensor sends it until it reaches a file, a Modbus register or your cloud.

A station does four things with every reading: it collects it, turns it into a parameter, stores it, and hands it on. Each step is set up on a different page of the console.

1. Collect

The station reads its sensors through its inputs:

InputSet up on
Modbus devices over RS-485, RS-232 or TCP (the station acts as the Modbus master)Modbus
SDI-12 sensorsSDI-12
Analog channels and digital inputsAnalog and digital
GPS and the station's own health (signal, supply, temperature)Built in

2. Turn readings into parameters

A parameter is one named value with a unit and a number of decimals, such as "GHI (W/m2)". Most parameters take a reading from an input and apply scaling and an offset. A calculated parameter is worked out from other parameters. Parameters are set up on the Parameters page; see also Calculated parameters.

The order of parameters on the Parameters page matters. It is the column order in downloaded files and the register order on the station's Modbus slave.

3. Store

The station keeps two kinds of data:

KindWhat it isSet on Device, Storage
Logged data (also called processed or minute data)One record per logging interval, for example every minute. What most people want.Update Interval from 1 to 60 minutes
Raw data (also called 1-second or instantaneous data)Readings at a short fixed interval, with a flag per value saying whether it was fresh.Turned on with Enable Raw Data Logging; Update Interval from 1 to 30 seconds

Records are grouped into files. Create Interval decides how much time one file covers: 1, 3, 6 or 12 hours, or 1 day (logged data can also use 1 month).

Data is written to the station's internal storage. If the station has an SD card fitted and turned on, it also keeps an archive there, and the files on the card are encrypted. See Data downloads.

When a sensor stops answering

If a sensor goes quiet, the station does not keep repeating its last value as if it were new. The value is marked stale and is written as NaN (not a number) in files, cloud uploads and Modbus registers, so a real reading of zero is never confused with "no data". You can switch this back to the older behaviour of writing 0 under Device, Storage, Stale Value Representation. See Device.

4. Hand it on

Way outWhat it doesRead more
Download from the consoleZIP files of CSV data for any date rangeData downloads, Download data
Modbus slaveA SCADA system or PLC reads the latest values from the station over Modbus TCP, RS-485 or RS-232Modbus slave register map
Aeron Cloud (Live3)The station uploads to Live3, where you see charts, alerts and reportsCloud upload
Cloud destinations (firmware 4.1 and later)The station sends data to your own service: HTTPS, Azure IoT Hub, Azure Event Hubs, AWS IoT Core, MQTT, SFTP or a TCP socketCloud destinations
USB driveWhen turned on under Device, Storage, plain CSV files are copied to a USB drive plugged into the stationDevice

A dropped network does not lose uploads. Each destination remembers how far it has got and, once the connection is back, sends everything it missed that is still stored on the station.

Time stamps

Every record carries the station's local date and time. If you change the station's time zone later, records already written keep the offset that was in effect when they were recorded. Keep the station's clock right with NTP or GPS; see Set the time.